8556 E SHASTA DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/25/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*
03/24/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) STEEL PIPING TO HAVE MINIMUM 12" COVER 2) VENTS FROM WATER HEATER AND FURNACE TO BE 3' ABOVE COOLER INTAKE WHEN WITHIN 10' 3) PROPER BONDING FOR BLDG GAS PIPING IS REQUIRED