Permit: T04PL00516

Parcel: 111060890

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
04/13/2004 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection 0000*/ CALL BACK ABOVE GRADE. OK TO COVER SITE WORK. TEST OK. COMPLETE C.O. TO GRADE FILL SEPTIC TANK COMPLETE VENT K-SINK.
04/12/2004 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY FOR INSP. 2) REQUIRE WTR TEST ON SEWER. 3) WIPING OF LEAKING FITTINGS NOT ACCEPTED METHOD OF REPAIRING LEAKS. CUT OUT FITTINGS AND REPLACE WITH NEW. 4) ABS IS NOT APPROVED IN EXPOSED EXTERIOR LOCATION. 2" VENT DOES NOT TERMINATE ABOVE ROOF. 5) SEPTIC TANK TO BE BROKEN AND INSP. BEFORE BACKFILLING.
04/07/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ NEW HCS AND TAP TO PROPERTY LINE ONLY - APPROX 35' ABS INSTALLED. OK TO COVER.
04/06/2004 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*/ PLEASE CALL AGAIN.