Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/17/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTION MADE. GAS CARD AT METER S.W. GAS 889-1888 |
| 03/16/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ WHERE UNIONS ARE REQUIRED A RIGHT/LEFT NIPPLE AND COUPLING SHALL BE USED. YOU REMOVED THE ½" UNION AS REQUESTED, BUT NOW YOU HAVE A UNION OUTSIDE THE WTR HTR. 2) OK TO BACKFILL TRENCH. PRESSURE TEST OK. |
| 03/12/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) A FLEX CONNECTOR MAY NOT PASS THROUGH THE METAL PARTITION. 2) REMOVE ½" UNION AND USE RIGHT/LEFT NIPPLE AND COUPLING. |
| 03/10/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) EXTEND 1" GAS PIPE TO FIRST BRANCH TEE OR PROVIDE APPROVED PLAN SHOWING 3/4" AS BEING ADEQUATE. 2) WATER HTR NOT RATED FOR OUTDOOR USE - PROVIDE ENCLOSURE. 3) MAKE ALL CONNECTIONS AND TEST ENTIRE SYSTEM. DO NOT TEST THRU APPLIANCES. 4) INSPECTION STOPPED. REQUIRED MIN. OF 12" OF COVER OVER PIPE. |