Permit: T04PL00474

Parcel: 124171750


Addresses:

1010 E 17TH ST

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
03/11/2004 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection 0000*/1) SOIL WTR TEST OK. 2) HCS CONNECTION IS OK. 3) YARD WTR TEST 50 LBS IS OK. 4) OK TO BACKFILL TRENCH.
03/09/2004 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection 0999*/1) WTR TEST SEEMS TO BE LOW. MUST HAVE TEST UP TO TWO WAY C.O. 2) EAST END OF SITE SEWER REQUIRES A MIN. OF 12" OF COVER CHECK FINAL SUB GRADE. 3) MUST PROVIDE AN AIR OR WTR TEST ON 1" PVC WTR SUPPLY. NOTE: PVC PRIMER APPEARS TO BE WEAK IN COLOR?