Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/04/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTION MADE. 10 PSI PRESSURE TEST FROM METER NEW 3/4" PE FROM METER TO AND THRU SERVICE VALVE AT BLDG EXISTING PIPING TO WTR HTR, STOVE, FURNACE AND GAS DRYER APPROVED. GAS CARD AT METER |
| 03/02/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PROVIDE AGA OR CSA APPROVED VALVES AT ALL LOCATIONS. 2) USE LEFT/RIGHT NIPPLE AND COUPLING WHERE UNIONS ARE NEEDED. 3) PROVIDE TRACER WIRE FOR UNDERGROUND PLASTIC PIPING. 4) PROVIDE BONDING OF GAS PIPING. |