Permit: T04PL00374

Parcel: 120032110


Addresses:

1031 W EBNER PL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/21/2004 PLUMBING - GAS PRESSURE TEST Approved CORRECTION MADE. NOW 1" SCOTCH COAT FROM METER UNDERGROUND TO WATER HEATER, 3/4 UP TO ROOF TOP UNIT AND STOVE. 17 PSI AIR TEST OK
05/17/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*/ 1) PROVIDE ROOF FLASHINGS AT PENETRATIONS THRU ROOF. 2) SUPPORT PIPING ON ROOF AT CORRECT INTERVALS AND CLAMP TO SUPPORTS. 3) PRIME AND TAPE ALL UNDERGROUND JOINTS AND TOOL MARKS ON PIPE. 4) RETEST AND HAVE MIN. 10 PSI TEST ON SYSTEM. 5) SUPPORT PIPING AT STOVE DROP.
04/19/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection 0000*
03/03/2004 PLUMBING - GAS PRESSURE TEST Denied
02/27/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*