Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000*/ 10 PSI TEST FROM METER EXISTING PIPING TO FURNACE, WTR HTR, STOVE APPROVED. ALL CORRECTIONS MADE. GAS CARD AT METER. 889-1888. |
| 03/01/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) UNION AT METER SHALL BE REPLACED BY LEFT-RIGHT NIPPLE AND COUPLING 2) PROVIDE PERMANENT CAP ON FURNACE VENT IN FURNACE CLOSET 3) PROVIDE PROPER BONDING FOR GAS PIPING 4) GAS TEST GAUGE TO BE IN 1/10 INCREMENTS TO PROVIDE MINIMUM 10 PSI PRESSURE TEST FOR 15 MINUTES TO OBSERVE ANY PRESSURE DROP 5) PROVIDE APPROVED CAP AT PIPING IN FURNACE CLOSET 6) COMBUSTIBLE VENTS WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE COOLER |