Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 03/04/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) WTR HTR FLU VENT IS OK. 4) FURNACE FLU VENT IS OK. |
| 02/27/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST USE REQUIRED PRESSURE GAUGE FOR AIR TEST. GUAGE MUST BE IN 1/10 INCREMENTS 2) MUST REMOVE UNIONS IN LINE AND REPLACE WITH RIGHT AND LEFT HAND NIPPLE 3) SHUT OFF VALVE FOR WATER CAN BE LOCATED 3'-0" MAXIMUM FROM REGULATOR OF DEVELOPER LENGTH 4) FLEX CONNECTOR CANNOT PENETRATE HOUSING OF FURNACE 5) MUST EXTEND FLU VENT FOR WATER HEATER 3'-0" ABOVE COOLER IF VENT IS LOCATED WITHIN 10'-0" OF COOLER 6) RE-TEST SYSTEM 10 POUNDS MINIMUM |