Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
Permit Number - T04PL00331
Inspection Description - PLUMBING - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)SHALL LOCATE SINGLE WALL FLU VENT CONNECTOR @ APPLIANCE COLLAR. THEN CONNECT TO DBL WALL OR RUN DBL WALL ALL THE WAY. 2)SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT AND @ APPLIANICE COLLAR 3)SHALL LOCATE GAS SHUT OFF VALVE WITHIN 3' OF REGULATER 4)SHALL PROVIDE 1" OF CLEARANCE AROUND COMBUSTIONABLE MATERIAL |
|
| 08/24/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SHALL PROVIDE WATER HTR 3" DBL WALL FLUE VENT MINIMUM OF 5' AND TERMINATE 1"-0" ABOVE EVE OF ROO W/CAP 2) SHALL TERMINATE T & P DRAIN 6" ABOVE FINISHED FLOOR 3) SHALL REPLACE T & P VALVE |