Permit: T04PL00331

Parcel: 138170060


Addresses:

320 E ELVIRA RD


Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Permit Number - T04PL00331

Inspection Description - PLUMBING - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
12/15/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)SHALL LOCATE SINGLE WALL FLU VENT CONNECTOR @ APPLIANCE COLLAR. THEN CONNECT TO DBL WALL OR RUN DBL WALL ALL THE WAY. 2)SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT AND @ APPLIANICE COLLAR 3)SHALL LOCATE GAS SHUT OFF VALVE WITHIN 3' OF REGULATER 4)SHALL PROVIDE 1" OF CLEARANCE AROUND COMBUSTIONABLE MATERIAL
08/24/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SHALL PROVIDE WATER HTR 3" DBL WALL FLUE VENT MINIMUM OF 5' AND TERMINATE 1"-0" ABOVE EVE OF ROO W/CAP 2) SHALL TERMINATE T & P DRAIN 6" ABOVE FINISHED FLOOR 3) SHALL REPLACE T & P VALVE