Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTION MADE. |
| 02/19/2004 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE. PLUMBER TO REMOVE FLEX AT RELIEF LINE AND HARD PIPE, ALSO CAULK. OK TO CALL GAS CO. 889-1888 CARD AT MATER SET |
| 02/18/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 13 PSI PRESSURE TEST FROM METER NEW 3/4" FROM METER TO WTR HTR AND FURNACE APP. 1) GAS PIPING TO BE SECURED PROPERLY IN FURNACE ROOM. 2) ROOF FLASHING AT GAS PIPE PENTRATION TO BE PROPERLY INSTALLED. 3) WTR HTR SHALL HAVE TEMPERATURE AND PRESSURE RELIEF INSTALLED AND GRAVITY DRAIN TO DAYLIGHT. 4) GAS PIPING TO BE PROPERLY BONDED. |