Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04PL00314

Parcel: 126110330


Addresses:

4313 E WHITMAN ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/20/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ CORRECTION MADE.
02/19/2004 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE. PLUMBER TO REMOVE FLEX AT RELIEF LINE AND HARD PIPE, ALSO CAULK. OK TO CALL GAS CO. 889-1888 CARD AT MATER SET
02/18/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 13 PSI PRESSURE TEST FROM METER NEW 3/4" FROM METER TO WTR HTR AND FURNACE APP. 1) GAS PIPING TO BE SECURED PROPERLY IN FURNACE ROOM. 2) ROOF FLASHING AT GAS PIPE PENTRATION TO BE PROPERLY INSTALLED. 3) WTR HTR SHALL HAVE TEMPERATURE AND PRESSURE RELIEF INSTALLED AND GRAVITY DRAIN TO DAYLIGHT. 4) GAS PIPING TO BE PROPERLY BONDED.