Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. |
| 02/18/2004 |
PLUMBING - FINAL |
|
Denied |
1) MUST REMOVE UNIONS IN LINE AT WTR HTR AND REPLACE WITH RIGHT/LEFT HAND NIPPLE. 2) MUST BLOCK UP GAS LINE ON ROOF AND USE APPROVED STRAPS. 3) MUST PROVIDE ROOF FLASHING. 4) MUST REMOVE FLEX CONNECTOR IN LINE FOR DRYER AND CONNECT TO ½" GAS LINE TO DRYER FOR A COMPLETE TEST ON SYSTEM. 5) T&P DRAIN CANNOT GO UP THRU ROOF. YOU CAN APPLY FOR A VARIENCE FORM AT OUR OFFICE FOR ALTERNATE METHOD OF INSTALLATION OF T&P DRAIN FOR WTR HTR. 6) RE-TEST SYSTEM. |