Permit: T04PL00312

Parcel: 120050190


Addresses:

902 W MACARTHUR ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/20/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE.
02/18/2004 PLUMBING - FINAL Denied 1) MUST REMOVE UNIONS IN LINE AT WTR HTR AND REPLACE WITH RIGHT/LEFT HAND NIPPLE. 2) MUST BLOCK UP GAS LINE ON ROOF AND USE APPROVED STRAPS. 3) MUST PROVIDE ROOF FLASHING. 4) MUST REMOVE FLEX CONNECTOR IN LINE FOR DRYER AND CONNECT TO ½" GAS LINE TO DRYER FOR A COMPLETE TEST ON SYSTEM. 5) T&P DRAIN CANNOT GO UP THRU ROOF. YOU CAN APPLY FOR A VARIENCE FORM AT OUR OFFICE FOR ALTERNATE METHOD OF INSTALLATION OF T&P DRAIN FOR WTR HTR. 6) RE-TEST SYSTEM.