Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTION MADE. |
| 02/17/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 10 PSI PRESSURE TEST FROM METER NEW 1" TO 3/4" TO WTR HTR AND 3/4" TO ROOF TOP UNIT APPROVED. 1) WTR HTR VENT TO BE INSTALLED CORRECTLY AND IF WITHIN 10' OF COOLER INTAKE BE EXTENDED 3' ABOVE COOLER. 2) PROVIDE PROPER BONDING ON BLDG GAS PIPING. 3) WTR HTR TO BE PERMITTED AND INSTALLED PROPERLY. |