Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 02/05/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000* |
| 02/04/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 10 PSI PRESSURE TEST TO BE ON ENTIRE GAS PIPING SYSTEM AT TIME OF INSPECTION. 1) APPROVED AGA OR CSA GAS VALVES TO BE INSTALLED ON EACH APPLIANCE. 2) THREAD PROTECTORS ARE NOT APPROVED COUPLING FITTINGS. REPLACE AND RETEST ENTIRE SYSTEM. CALL BACK IN FOR INSP. 3) PROVIDE PROPER BONDING OF GAS PIPING. |