Permit: T04PL00217

Parcel: 138100700

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04PL00217

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HEATER FLUE VENT, T & P VALVE IS OK
02/25/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) SEE NOTE #1 TEST ENTIRE SYSTEM FROM METER LOCATION TO ALL OF SYSTEM FOR TRAILER 2) CANNOT HAVE A FLEX CONNECTIOR PENETRATE WATER HEATER ENCLOSURE. MUST HARD PIPE INTO ENCLOSURE, THE CONNECT VALVE AND FLEX LINE 3) MUST CUT OFF THREADS AT BOTTOM OF T & P DRAIN
02/04/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) MUST PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM WITH 10 LBS MIN. 2) MUST PROVIDE A WTR HTR ENCLOSURE FOR WTR HTR AND PROVIDE FLU VENT AND CAP 5'0". 3) MUST EXTEND T&P DRAIN 3/4" ALL THE WAY AND TERMINATE DRAIN 6" ABOVE FLOOR. 4) MAKE SURE ALL GAS SHUT OFF VALVES ARE AGA OR CSA APPROVED.