Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/02/2004 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection :*/WATER TEST FROM DRAIN TO INTERCEPTOR OK. WATER TEST FROM INTERCEPTOR TO HCS CONNECTION OK. HCS CONNECTION OK. |
| 11/01/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection :*/1)PROVIDE CORRECT FALL ON INTERCEPTOR DRAIN TO POINT OF CONNECTION TO EXISTING 2)PROVIDE CORRECT TRANSITION BLDG FROM ABS TO PVC ON STD BUSHING AT INLET & OUTLET OF INTERCEPTOR 3)DRAINAGE FITTINGS REQUIRED AT VENTS FOR HORIZONTAL VENTING BELOW FLOOD RIM OF FIXTURE 4)MAKE CONNECTION TO AREA DRAIN AND PROVIDE TEST. OK TO COVER FROM TIE IN AT PROPERTY LINE TO FENCE AREA |