Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/08/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) NOTE: KITCHEN RANGE IS NOT INSTALLED @ THIS TIME. |
| 02/20/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999/ 1) MUST BLOCK AND STRAP GAS LINE ON ROOF WITH APPROVED STRAPS EVERY 6'. 2) NOTE: NO ONE HOME! THERE COULD BE MORE CODE VIOLATIONS THAT I CAN NOT SEE AT THIS TIME.GO OVER SYSTEM AND BRING SYSTEM TO CODE. 3) MUST PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM. 4) MUST CONNECT WATER HTR FLU VENT WITH THREE SHEET METAL SCREWS PER JOINT. |