Permit: T04PL00070

Parcel: 133040960

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/16/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 13 psi test is leaking. 3/4" pipe may not be adequate for 4 appliances. draw up a plan with pipe sizes, distance from meter and total btu demand. submit to plan check for approval. recall for inspection.