4001 E WHITMAN ST

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/25/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) NO WTR TEST ON SYSTEM. 2) USE DRAINAGE FITTINGS NOT VENT FITTINGS AT WALL PENETRATIONS. REMOVE FURNEO COUPLINGS AND REPLACE WITH SOLVENT WELD FITTINGS. 3) ALL DRAINAGE PIPING TO HAVE 2% GRADE. 4) CONTRACTOR - OWNER IS AWARE THAT ABS MAY NOT BE USED IN EXPOSED EXTERIOR LOCATIONS, AND ASKED IF PAINTING IS OK. INSPECTION STOPPED.
01/15/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ PROVIDE WATER TEST. REMOVE WATER PIPE FITTING. provide drainage fitting.