Permit: T04PL00041

Parcel: 106060180


Addresses:

1280 W PRINCE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04PL00041

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/14/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK. 2) OK FOR GAS 3) UCC LEFT AT METER SET.
01/13/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) ALL GAS PIPING TO BE SUPPORTED TO TABLE 12-2 AND TABLE 3-1. ALL VALVES TO BE WITHIN THREE FT OF CONNECTION. 2) THE CONDENSATE WASTE PIPING IS MADE OF UNPROTECTED MATERIAL WITH NO TRAPS, NO SUPPORT, AND DUMPING ONTO ROOF. YOU MAY WANT TO LOOK AT THIS.
01/12/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ SEE 103.5.4 SECOND PARAGRAPH. SEE 103.5.4.2 RESPONSIBILITY. LADDER LEFT FOR INSPECTOR NOT SAFE TO USE.
01/09/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ SUPPORT VERTICAL PIPE ON EXTERIOR WALL. 2) SEAL AND WATERPROOF OPENING AT EXTERIOR. 3) NO ACCESS TO ROOF.