Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04PL00041
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK. 2) OK FOR GAS 3) UCC LEFT AT METER SET. | |
01/13/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) ALL GAS PIPING TO BE SUPPORTED TO TABLE 12-2 AND TABLE 3-1. ALL VALVES TO BE WITHIN THREE FT OF CONNECTION. 2) THE CONDENSATE WASTE PIPING IS MADE OF UNPROTECTED MATERIAL WITH NO TRAPS, NO SUPPORT, AND DUMPING ONTO ROOF. YOU MAY WANT TO LOOK AT THIS. | |
01/12/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ SEE 103.5.4 SECOND PARAGRAPH. SEE 103.5.4.2 RESPONSIBILITY. LADDER LEFT FOR INSPECTOR NOT SAFE TO USE. | |
01/09/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ SUPPORT VERTICAL PIPE ON EXTERIOR WALL. 2) SEAL AND WATERPROOF OPENING AT EXTERIOR. 3) NO ACCESS TO ROOF. |