Permit: T04PL00014

Parcel: 11714355B


Addresses:

580 S MAIN AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/23/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK. 2) WATER HTR FLU VENT, T&P VALVE AND DRAIN IS OK. 3) GAS SHUT OFF VALVES OK. 4) NOTE: THERE ARE NO GAS APPLIANCES INSIDE DWELLING.
01/21/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*/ 1) MUST PROVIDE AIR PRESSURE GAUGE WITH 1/10 INCREMENTS.. 2) MUST REMOVE FLEX LINE IN T&P DRAIN AND REPLACE OLD T&P VALVE NOT WORKING. 3) MUST SCREW DOWN WATER HTR FLU VENT WITH 3 SHEET METAL SCREWS PER JOINT.
01/13/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*/ NOT READY FOR INSPECTION.