Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/27/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) ALL CORRECTIONS HAVE BEEN MADE |
| 01/26/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ DOORS AND GATES WERE LOCKED. |
| 01/16/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ PROVIDE FLASHING AT ROOF PENETRATION AND BONDING FOR GAS PIPING. PROVIDE UPPER COMBUSTION AIR IN DOOR OF WATER HEATER ENCLOSURE. |
| 01/06/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM 10 LBS MIN. 2) MUST PROVIDE GAS SHUT OFF VALVE FOR GAS PACK ON ROOF LOCATED 3'0" MAX FROM UNIT. 3) MUST BLOCK AND STRAP GAS LINE ON ROOF EVERY 6" 4) MUST HARD PIPE GAS LINE INTO WTR HTR ROOM THEN CONNECT SHUT OFF VALVE AND FLEX CONNECTOR. 5) MUST SEAL HOLES IN SIDE WALLS OF WTR HTR ENCLOSURE AND PROVIDE A DOOR WITH 2 - 10X10 LOUVER GRILLS ON DOOR LOCATED 12" ABOVE FLOOR AND 12" BELOW CEILING. 6) MUST EXTEND T&P VALVE DRAIN WITH 3/4" AND TERMINATE 6" ABOVE FLOOR. |