Permit: T04PL00011

Parcel: 120084930


Addresses:

4633 S 12TH AV #02

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/27/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) ALL CORRECTIONS HAVE BEEN MADE
01/26/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ DOORS AND GATES WERE LOCKED.
01/16/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ PROVIDE FLASHING AT ROOF PENETRATION AND BONDING FOR GAS PIPING. PROVIDE UPPER COMBUSTION AIR IN DOOR OF WATER HEATER ENCLOSURE.
01/06/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) MUST PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM 10 LBS MIN. 2) MUST PROVIDE GAS SHUT OFF VALVE FOR GAS PACK ON ROOF LOCATED 3'0" MAX FROM UNIT. 3) MUST BLOCK AND STRAP GAS LINE ON ROOF EVERY 6" 4) MUST HARD PIPE GAS LINE INTO WTR HTR ROOM THEN CONNECT SHUT OFF VALVE AND FLEX CONNECTOR. 5) MUST SEAL HOLES IN SIDE WALLS OF WTR HTR ENCLOSURE AND PROVIDE A DOOR WITH 2 - 10X10 LOUVER GRILLS ON DOOR LOCATED 12" ABOVE FLOOR AND 12" BELOW CEILING. 6) MUST EXTEND T&P VALVE DRAIN WITH 3/4" AND TERMINATE 6" ABOVE FLOOR.