| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2005 | SIGN ELECTRIC | Approved | IVRS - Inspection :* | |
| 05/04/2005 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1) SWITCH POWER TO BE ISOLATED TO SWITCH 2) SUPPORT GT0 CABLE AND INSTALL WITH CODE CLEARANCES 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 4) PLEASE USE ALL STRANDS OF GTO CABLE 5) TIGHTEN HIGH VOLTAGE TERMINATIONS 6) BOND TRANSFORMER ENCLOSURERS 7) PLEASE PROVIDE CITY STICKER TABS |