Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04OT02518

Parcel: 12510009H


Addresses:

3832 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
05/06/2005 SIGN ELECTRIC Approved IVRS - Inspection :*
05/04/2005 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
1) SWITCH POWER TO BE ISOLATED TO SWITCH
2) SUPPORT GT0 CABLE AND INSTALL WITH CODE CLEARANCES
3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING
4) PLEASE USE ALL STRANDS OF GTO CABLE
5) TIGHTEN HIGH VOLTAGE TERMINATIONS
6) BOND TRANSFORMER ENCLOSURERS
7) PLEASE PROVIDE CITY STICKER TABS