Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T04OT02438
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2005 | SIGN SHOP | Approved | IVRS - Inspection :* | |
05/03/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
05/02/2005 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
04/27/2005 | SIGN SHOP | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
03/16/2005 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1) PER MANUFACTURERS INSTRUCTION MASTERS TECHNOLOGY PRODUCTS ARE NOT TO BE PAINTED. 2) TERMINAL END ARE ONLY LISTED FOR 600 VOLTS CABLE IS 15000 VOLTS. BUILDING HAS LIGHTING POSITIONED UPWARD TO SIGN THAT DOES NOT MEET LIGHTING CODES. | |
03/02/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) SLEEVING TO BE LISTED FOR OUTDOOR/ WEATHER PROOF 2) FINISH INSTALLATION NEON AND PREVIOUS INSPECTION REQUEST | |
02/07/2005 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1) GTO CABLE NOT TO CROSS AND CONTACT OTHER CABLE OR BOOTS. 2) FILL UNUSED OPENING IN BOX COVER. 3) PLEASE VERIFY SIGN CIRCUITING PER 600.5 4) TERMINAL END TO BE LISTED FOR OUTER 600 VOLTS. 5) PRIMARY CONDUCTORS TO BE ISOLATED TO SWITCH PER STAMPED PLANS. |