Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T04OT02304
Inspection Description - FIRE - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2005 | FIRE - FINAL | Denied | TFC 1008.1.8.3 Remove double cylinder keyed dead bolt lock from rear kitchen exit door, not allowed to have key operated locks on exit doors. TFC 904.11.6.4 Hood systems shall be inspected every 6 months. System is past due, last inspection shows 11/2003. TFC 610.1 All cooking appliances shall be 6 inches under hood system. TFC 605.6 Cover plate is needed on outlet in back storage room. TFC 605.5 Extension cord to microwave not allowed Extension cord to juke box player not allowed Extension cord to open sign not allowed, also replace flex cord to sign ground lugs can not be cut off GROUND LUG. ADDRESS NUMBERS ON BUILDING |