Inspection Status: Approved
Inspection History: SIGN SHOP
| Date |
Description |
Inspector |
Results |
Comments |
| 01/27/2005 |
SIGN SHOP |
|
Approved |
IVRS - Inspection :* |
| 01/10/2005 |
SIGN SHOP |
|
Partial Approval |
IVRS - Inspection :*1) BOND RACEWAY ENCLOUSER CHECK ON SITE. |
| 01/06/2005 |
SIGN SHOP |
|
Not ready for Inspection |
IVRS - Inspection :*/1)USE APPROVED CONNECTIONS FOR 15000 V 2)TIGHTEN TERMANAL CONNECTIONS 200 HOUSINGS 3)BOND RACE WAY ENCLOUSER 600.7 5)MAINTAIN 1 1/2" CLEARENCES AT HIGH VOLTAGE TERMANATIONS 6)GTO LENGTH HASTOO MUCH SLACK 7)JUNCTION BOX TO BE ACCESSABLE |
| 01/04/2005 |
SIGN SHOP |
|
Not ready for Inspection |
IVRS - Inspection :* |