Permit: T04OT02187

Parcel: 13010001A


Addresses:

3102 E 22ND ST


Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T04OT02187

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
01/13/2005 SIGN ELECTRIC Approved IVRS - Inspection :*
11/18/2004 SIGN ELECTRIC Partial Approval IVRS - Inspection :*/1)NEED MARKING LABELS 600.4 2)BOND JUNCTION BOX & TRANSFORMER ENCLOUSER 250-148 & 600.7
3)FILL UNUSED OPENING IN RACK WAY 4)FINISH POWER SUPPLY
11/17/2004 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
11/16/2004 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*