Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04OT02187

Parcel: 13010001A


Addresses:

3102 E 22ND ST

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
01/13/2005 SIGN ELECTRIC Approved IVRS - Inspection :*
11/18/2004 SIGN ELECTRIC Partial Approval IVRS - Inspection :*/1)NEED MARKING LABELS 600.4 2)BOND JUNCTION BOX & TRANSFORMER ENCLOUSER 250-148 & 600.7
3)FILL UNUSED OPENING IN RACK WAY 4)FINISH POWER SUPPLY
11/17/2004 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*
11/16/2004 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*