Permit: T04OT02093

Parcel: 131090060


Addresses:

5802 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/29/2005 MECHANICAL - FINAL Approved IVRS - Inspection :* OK FOR FINAL C OF O
11/09/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/TYPE I EXHAUST FANS ON ROOF ARE NOT WIRED CORRECTLY & BOTH FANS MUST BE INTERLOCKED WITH THE MAKE UP AIR UNIT. EXCESSIVE GREASE NEEDS TO BE CLEANED OFF OF FAN. & ROOF. GREASE CUPS ARE REQUIRED ON EACH FAN