Inspection History Details
Inspection Status: Closed
Inspection History: SIGN SHOP
Permit Number - T04OT01730
Inspection Description - SIGN SHOP
Inspection Status - Closed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2008 | SIGN SHOP | Closed | SIGN HAS BEEN REMOVED | |
| 04/23/2007 | SIGN SHOP | Denied | IVRS - Inspection : 1. A MARKING LABEL IS NEEDED 2. SWITCH TO BE CAPABLE OF BEING LOCKED OUT 3. BOND LETTERS CORRECTLY 4. BOND/GROUND JUNCTION BOXES 5. BOX IS OVERFILLED 6. USE APPROVED FITTINGS WITH SEAL TITE 7. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |
|
| 04/12/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 03/25/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
| 03/23/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
| 03/09/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY STACE - NO PAPERWORK |
|
| 12/07/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY STACE |
|
| 06/12/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* |