Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/OK FOR FINAL C/O | |
| 12/14/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : 1) PROVIDE A FRESH AIR INTAKE ON A/C UNIT. BE SURE TO PROVIDE A FILTER. 2) TERMINATE CONDENSATE TO A FLOOR DRAIN. CANNOT TERMINATE ONTO A HARD SURFACE. PAINT EXPOSED PVC W/LATEX PAINT. 3) MARK UNIT DATE PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. RECALL FOR INSPECTION |