Inspection Status: Approved
Inspection History: SIGN SHOP
| Date |
Description |
Inspector |
Results |
Comments |
| 09/14/2004 |
SIGN SHOP |
|
Approved |
IVRS - Inspection :*/ 1) OK SIGN |
| 09/08/2004 |
SIGN SHOP |
|
Partial Approval |
IVRS - Inspection :*/ 1) AN ACCESS AS PER 600.21 (E) IS NEEDED 2) SUPPORT GTO CABLE UP OFF OF RACEWAY 3) GROUND RACEWAY 4) TIGHTEN G TO TERMINATIONS 5) SWITCH TO BE AS PER 600.6-A LOCKOUT IS ALLOWED |
| 09/02/2004 |
SIGN SHOP |
|
Not ready for Inspection |
IVRS - Inspection :NO SIGN CONTRACTOR LISTED FOR SHOP - CUSTOMER STATES RAINBOW SIGNS IS DOING WORK |