Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/02/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ACCESSIBLE ROUTES MUST HAVE "NO KNOWLEDGE" HARDWARE. THAT MEANS LEVER HANDLES AND AUTOMATIC UNLOCKING FROM EGRESS SIDE 2) PVC CONDUIT AND ELECTRIC WIRING OVER FRONT DOOR DOES NOT MEET CODE REQUIREMENTS 3) BATHROOM DOES NOT MEET ADAAG CLEAR FLOOR SPACE REQUIREMENTS AT WATER CLOSET OR LAVATORY 4) THERE ARE NO ADA COMPATIBLE BATHING FACILITIES 5) EMERGENCY EGRESS LIGHTING DOES NOT MATCH PLAN 6) MECHANICAL DUCTING ADDED WITHOUT PERMITS (THROUGH LAUNDRY) 7) WATER HEATER (1997) INSTALLED WITHOUT PERMIT IS LACKING TPRV DISCHARGE LINE AND COLD WATER SHUT OFF 8) RAMPS REQUIRE HAND RAILS OR SIDE APRONS THAT SLOPE NO MORE THAN 1:10 |