Permit: T04OT01272

Parcel: 12511160B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04OT01272

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/28/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) DISCONNECTS TO BE ADDRESSED - UNIT #'S. 2) OVERHEAD SERVICE CONDUCTORS NEED TO BE INSULATED AT SPLICE. 3) DISCONNECT NEXT TO #10 CANNOT HAVE DBL LUGGING. 4) REMOVE UNUSED WIRE AT SERVICE 5) NORTH SIDE PANEL ROOM - OPEN J-BOX. 6) SERVICE TO POOL EQUIPMENT NOT GROUNDED - POOL EQUIPMENT AREA, LIGHT OPEN SPLICED OPEN ROMEX TO BE IN CONDUIT, 7) VERIFY SMOKE DETECTOR IN ALL UNITS. 8) PANELS TO HAVE INDIVIDUAL CIRCUITS MARKED FOR UNITS.