Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04OT01139
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2004 | MECHANICAL - FINAL | Approved | ||
| 06/09/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) VENT CONNECTOR ON FURNACE NOT ATTACHED TO FLUE PIPE. PROVIDE 3 SCREWS IN CONNECTION. 2) FLUE PIPE DOES NOT HAVE 1" MIN. CLEARANCE FROM COMBUSTABLES AT PENETRATION THRU ROOF. CORRECT AND RECALL FOR FINAL INSP. |