Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T04OT01110
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2004 | SIGN ELECTRIC | Approved | IVRS - Inspection :*/ OK SIGN. | |
06/24/2004 | SIGN ELECTRIC | Partial Approval | IVRS - Inspection :*/ 1) SWITCH FOR SIGN TO BE AS PER 600.6 A LOCKABLE DEVICE. 2) NO POWER AT THIS TIME. 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. 4) SEAL UNUSED OPENINGS IN TRANSFER CASE - GROUNDS. 5) BOND SEAL TITE PER 600-7. |