Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 06/28/2004 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection :*/ OK SIGN. |
| 06/24/2004 |
SIGN ELECTRIC |
|
Partial Approval |
IVRS - Inspection :*/ 1) SWITCH FOR SIGN TO BE AS PER 600.6 A LOCKABLE DEVICE. 2) NO POWER AT THIS TIME. 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. 4) SEAL UNUSED OPENINGS IN TRANSFER CASE - GROUNDS. 5) BOND SEAL TITE PER 600-7. |