Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T04OT01110

Parcel: 13355231A

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
06/28/2004 SIGN ELECTRIC Approved IVRS - Inspection :*/ OK SIGN.
06/24/2004 SIGN ELECTRIC Partial Approval IVRS - Inspection :*/ 1) SWITCH FOR SIGN TO BE AS PER 600.6 A LOCKABLE DEVICE. 2) NO POWER AT THIS TIME. 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. 4) SEAL UNUSED OPENINGS IN TRANSFER CASE - GROUNDS. 5) BOND SEAL TITE PER 600-7.