Inspection History: SIGN ELECTRIC

Permit Number - T04OT01110

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2004 SIGN ELECTRIC Approved IVRS - Inspection :*/ OK SIGN.
06/24/2004 SIGN ELECTRIC Partial Approval IVRS - Inspection :*/ 1) SWITCH FOR SIGN TO BE AS PER 600.6 A LOCKABLE DEVICE. 2) NO POWER AT THIS TIME. 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. 4) SEAL UNUSED OPENINGS IN TRANSFER CASE - GROUNDS. 5) BOND SEAL TITE PER 600-7.