Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T04OT01070
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2004 | SIGN ELECTRIC | Approved | IVRS - Inspection :*/ 1) OK SIGN | |
07/28/2004 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :*/ 1) FINISH PREVIOUS ITEMS | |
07/26/2004 | SIGN ELECTRIC | Partial Approval | IVRS - Inspection :NEED MARKUP LABEL PER 600-4 |