Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/ 1) CORRECTIONS HAVE BEEN MADE AS PER LAST REQUEST 2) PLEASE NOTE PROVIDE TESTING ON BACK FLOW DEVICE FOR WATER DEPT | |
| 05/24/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ALL COMMERCIAL WATER CLOSETS TO BE ENLONGATED BOWEL WITH OPEN FRONT SEAT 2) KITCHEN SINK REQUIRES A CLEANOUT-OPEN DRAIN BACK PITCH 3) JANITOR SINK NOT HOOKED UP-OPEN DRAIN NO CLEANOUT 4) AT OUTSIDE LAVATORIES-ABS IS NOT APPROVED IN EXPOSED EXTERIOR LOCATION 5) I DIDN'T SEE THE RPPBP ON THE WATER LINE 6) NO EXPANSION TANK ON WATER HEATER |