Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/09/2004 |
ELECTRIC - FINAL |
|
Approved |
|
| 05/21/2004 |
ELECTRIC - FINAL |
|
Denied |
1) SERVICE OR REPLACE ALL SMOKE DETECTORS. THEY MUST ALARM ON TEST 2) CLEAR OUT THE ELECTRIC CLOSET OF BLDG EAST AND HAVE EXPOSED CABLES COVERED WITH A REMOVABLE PLYWOOD PANEL 3) INSTALL A BLANK COVER OVER THE "LB" ELECTRICAL FITTING AT ELECTRICAL SERVICE PANEL ON WEST SIDE OF WEST OFFICE BLDG 4) IDENTIFY AND MARK ALL CIRCUITS IN THE CIRCUIT BREAKER PANELS OF BOTH BLDGS 5) INSTALL GFCI RECEPTACLES AT KITCHEN COUNTER AND OTHER SIMILAR LOCATIONS WHERE RECEPTACLES ARE LOCATED NEAR ANY SINK. ALL EXTERIOR RECEPTACLES MUST BE OF THE GFCI TYPE |