Permit: T04OT00933

Parcel: 111050370

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/09/2004 ELECTRIC - FINAL Approved
05/21/2004 ELECTRIC - FINAL Denied 1) SERVICE OR REPLACE ALL SMOKE DETECTORS. THEY MUST ALARM ON TEST 2) CLEAR OUT THE ELECTRIC CLOSET OF BLDG EAST AND HAVE EXPOSED CABLES COVERED WITH A REMOVABLE PLYWOOD PANEL 3) INSTALL A BLANK COVER OVER THE "LB" ELECTRICAL FITTING AT ELECTRICAL SERVICE PANEL ON WEST SIDE OF WEST OFFICE BLDG 4) IDENTIFY AND MARK ALL CIRCUITS IN THE CIRCUIT BREAKER PANELS OF BOTH BLDGS 5) INSTALL GFCI RECEPTACLES AT KITCHEN COUNTER AND OTHER SIMILAR LOCATIONS WHERE RECEPTACLES ARE LOCATED NEAR ANY SINK. ALL EXTERIOR RECEPTACLES MUST BE OF THE GFCI TYPE