Inspection History: SIGN ELECTRIC
Permit Number - T04OT00929
Inspection Description - SIGN ELECTRIC
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2004 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :*/ 1) ACCESS TO BE AS PER 600-21. 2) THHN IS NOT AN APPROVED METHOD FOR SUPPORTING M/C CABLE. 3) NO CIRCUIT IS PROVIDED AS PER 600.5. 4) PROTECT CONDUCTOR THRU COMBUSTABLE WOOD AND AT ENTRANCE TO RACEWAY. | |
06/16/2004 | SIGN ELECTRIC | Partial Approval | IVRS - Inspection :*/ OK NORTH SIGN CALL WHEN WEST SIGN READY. |