Inspection Status: Not ready for Inspection
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/18/2004 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) THIS HOME IS SUITABLE FOR AN R-3 OCCUPANCY OF MAX FIVE CLIENTS 2) C OF O ISSUED IN 1998 IS FOR R-3 WITH MAX 8 CLIENTS. I BELIEVE THIS SI AN ERROR 3) FOR AN R-4 (MORE THAN 5 CLIENTS) YOU NEED A) 2 EXITS (PROVIDED-3) B) 1 EXIT MUST MEET CHAPTER 11 IBC ACCESSIBILITY REQUIREMENTS; IE THRESHOLDS ETC. C) SMOKE ALARMS MUST BE INTER CONNECTED D) ANTI-SCALD VALVES IN BATHROOMS REQUIRED E) YOU NEED TO HAVE AN ACCESSIBLE RESTROOM PER CHAPTER 11 IBC 4) FOR AN R-4 OCCUPANCY (GREATER THAN 5 CLIENTS). PLEASE RESUBMIT PLANS SHOWING ACCESSIBLE EGRESS ROUTE, ACCESSIBLE RESTROOMS AND EMERGENCY EGRESS LIGHTING |