Permit: T04OT00861

Parcel: 12511160B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04OT00861

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/OK FOR FINAL C/O
06/28/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ REPAIR VENT CONNECTORS ON WTR HTRS. PROVIDE 3 SCREWS IN EACH JOINT. PROVIDE 6" CLEARANCE FROM COMBUSTABLES. SUPPORT PROPERLY. PROVIDE T&P DRAINS ON WTR HTRS. T&P VALVES NOT WORKING. IF USING THREADED PIPE, DO NOT HAVE THREADS ON BOTTOM PIECE. REPLACE FURNACE VENT ON ROOF UNIT #8. PROVIDE A LOW COMBUSTION AIR OPENING IN WTR HTR ROOM. FURNACES ARE EXISTING WALL HTRS.