Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04OT00861
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/OK FOR FINAL C/O | |
| 06/28/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ REPAIR VENT CONNECTORS ON WTR HTRS. PROVIDE 3 SCREWS IN EACH JOINT. PROVIDE 6" CLEARANCE FROM COMBUSTABLES. SUPPORT PROPERLY. PROVIDE T&P DRAINS ON WTR HTRS. T&P VALVES NOT WORKING. IF USING THREADED PIPE, DO NOT HAVE THREADS ON BOTTOM PIECE. REPLACE FURNACE VENT ON ROOF UNIT #8. PROVIDE A LOW COMBUSTION AIR OPENING IN WTR HTR ROOM. FURNACES ARE EXISTING WALL HTRS. |