Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04OT00861
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/28/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*1) DISCONNECTS TO BE ADDRESSED - UNIT #'S. 2) OVERHEAD SERVICE CONDUCTORS NEED TO BE INSULATED AT SPLICE. 3) DISCONNECT NEXT TO #10 CANNOT HAVE DBL LUGGING. 4) REMOVE UNUSED WIRE AT SERVICE 5) NORTH SIDE PANEL ROOM - OPEN J-BOX. 6) SERVICE TO POOL EQUIPMENT NOT GROUNDED - POOL EQUIPMENT AREA, LIGHT OPEN SPLICED OPEN ROMEX TO BE IN CONDUIT, 7) VERIFY SMOKE DETECTOR IN ALL UNITS. 8) PANELS TO HAVE INDIVIDUAL CIRCUITS MARKED FOR UNITS. |