Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 07/14/2004 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection :*/ 1) OK SIGN |
| 07/13/2004 |
SIGN ELECTRIC |
|
Partial Approval |
IVRS - Inspection :*/ 1) CONDUCTOR TO BE COLORED FOR VOLTAGE-277V 2) SWITCH TO BE LOCKABLE 600.6 3) WHERE IS MARKING LABEL 600.4-#2 PREVIOUS INSPECTION |