Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04OT00660

Parcel: 13355230A


Addresses:

9565 E 22ND ST #127


Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T04OT00660

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2004 SIGN ELECTRIC Approved IVRS - Inspection :*/ OK SIGN.
06/24/2004 SIGN ELECTRIC Partial Approval IVRS - Inspection :*/ 1) SWITCH FOR SIGN TO BE AS PER 600-6. - A LOCKABLE DEVICE IS ALLOWED. 2) NO POWER AT THIS TIME . 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. 4) SEAL UNUSED OPENINGS IN TRANSFORMER CASE - GROUNDS. 5) BOND SEAL TITE PER 600-7.