Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04OT00421
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/24/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) RECEPTACLE TO BE MOUNTED UP ABOVE CLASSIFIED AREA OR INSTALL AS FOR CLASSIFIED AREA. 2) FILL UNUSED OPENINGS IN PANEL AND BOXES. 3) RECEPTACLE TO BE GFCI PROTECTED IN SHOP. 4) USE CORRECT COVER PLATES. 5) FUSES FOR CONDUCTOR ANPACITY AT MAIN DISCONNECT. 6) PROPERLY INSTALL SPLICE TAP AND TIGHTEN LOOSE TERMINALS. |