Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2004 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 05/17/2004 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
| 05/05/2004 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) USE APPROVED MEANS TO SEAL UNUSED OPENINGS. 2) CORRECTLY TERMINATE G TO GABLE TO PK HOUSING CONNECTION. 3) COMBUSTABLES (HANKERCHIEF) NOT TO BE LEFT IN RACEWAY. 4) MISSING SPLICE BOOT IN LETTER. 5) FINISH ITEMS 5, 8, 9, 10, 12 OF PREVIOUS INSPECTION. |
|
| 04/23/2004 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) USE APPROVED FITTINGS WITH SEAL TITE 2) CANNOT ENTER THROUGH ACCESS COVER 3) PRIMARY CONDUCTOR TO BE AS STAMPED ON PLANS 4) SUPPORT SEAL TITE AS PER CODE 5) BOND RACEWAY ENCLOSURE 600.7 7) MISSING RACEWAY COVER 8) PROPERLY TERMINATE PK HOUSING CONNECTIONS 9) SECURELY MOUNT RACEWAY TO WALL ONLY 2 1/4" TAP CONS NOT PER PLANS 10) MAINTAIN GTO CABLE SPACING AND CLEARANCES 600.32 11) WHERE IS SIGN MARKING LABEL 600.4 12) WHERE IS 2ND PK HOUSING AT LETTERS AS PER PLANS |