Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04OT00303

Parcel: 133153420


Addresses:

1853 N KOLB RD

Inspection Status: Partial Approval

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
04/22/2004 SIGN ELECTRIC Partial Approval IVRS - Inspection :*
04/22/2004 SIGN ELECTRIC Approved IVRS - Inspection :*
03/29/2004 SIGN ELECTRIC Denied IVRS - Inspection 0999*/ 1) SPLICE BOOTS TO BE LISTED FOR WEATHER PROOF APPLICATION. 2) SUPPORT FLEX CONDUIT AS PER CODE. 3) TIGHTEN LOOSE FITTINGS. 4) SECURE BALLAST TO CASE. 5) GROUND ENCLOSURE.