Permit: T04OT00152

Parcel: 115180050


Addresses:

1601 N ORACLE RD

Inspection Status: Closed

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/20/2007 PLUMBING - FINAL Closed
02/02/2004 PLUMBING - FINAL Denied IVRS - Inspection 0922*/ 1) A C OF O IS ISSUED FOR A BLDG; NOT FOR AN INDIVIDUAL ROOM OR ROOMS WITHIN A BLDG EVEN ON A T.I. A C OF O CANNOT BE ISSUED UNTIL THE SHELL HAS BEEN FIANLED. IN THIS CASE THE "SHELL" HAS NUMEROUS CODE VIOLATIONS; HOWEVER, ALL C OF O'S ARE TO BE CLEARED THROUGH STEVE LONG
01/28/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ THIS INSPECTION IS FOR COMMON BLDG ONLY. 1) VACUUM BREAKERS REQUIRED ON ALL HOSE BIBS. 2) IN KITCHEN - ALL INDIRECT WASTE PIPING TO CONFORM TO 94 UPC - MAY NOT BE COMBINED. OVER FIVE FEET REQUIRED TO BE DIRECTLY TRAPPED. APPROVED MATERIAL REQUIRED. APPROVED AIR GAP REQUIRED. GAS VALVES TO BE AGA OR CSA APPROVED. NO QUICK DISCONNECTS OR CABLE RESTRAINTS ON MOVABLE EQUIPMENT. OPEN FLOOR DRAIN. 3) EACH PIECE OF WATER SUPPLIED EQUIPMENT, IE: TEA BREWERS, COFFEE MAKERS, SODA FOUNTAINS ETC TO HAVE OWN BACKFLOW DEVISE. DRAINS TO BE INSTALLED PER 94 UPC. 4) DRAIN PIPES MAY NOT BE REDUCED.