Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/25/2004 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* EXSISTING BLDG OCCUPIED FOR SAME PURPOSE SINCE 1948 WITH AN ADDITION IN 1967. BLDG REQUIRES SOME NORMAL MAINTENANCE BUT COMPLIES WITH CODE FOR NON-SEPARATED USE AND CHAPTER 34 EXSISTING BLDG REQUIREMENTS. EXCEPT IN INTEREST OF LIFE SAFTY. 1) INSTALL SIGN OVER MARKET ENTRANCE"THIS DOOR TO REAMIN UNLOCKED WHILE BLDG IS OCCUPIED." 2) EXIT DOORS OUT OF TORTILLA BAKERY TO OPEN OUTWARD & HAVE ONLY THUMB OPERATED DEADBOLTS FOR LOCKING. 3) INSTALL EMERGENCY EGRESS LIGHTING & ILLUMINATED EXIT SIGNS. |
| 02/23/2004 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/23/2004 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 01/21/2004 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* BUILDING DOES NOT CONFORM TO PLAN FROM 1967 (FIRE SEPARATION WALL) NEED MORE INFORMATION. |