Inspection Status: Not ready for Inspection
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 05/17/2004 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) DISCONNECT SWITCH TO BE WITHIN SIGHT OF SIGN, 600-6, NOT ON ROOF. 2) FILL UNUSED OPENINGS IN FLOURESCENTS AND LOGO SIGN. 3) PLANS AND PERMIT CAN NOT BE FOUND. NEED TO SEE. |
| 05/10/2004 |
SIGN ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) PLANS AND PERMITS NOT ON SITE. 2) A DISCONNECT SWITCH IS NEEDED FOR FLOURECENT SIGNS ON BLDG AND LOGO SIGN 600-6. 3) FILL UNUSED OPENINGS IN SIGN AND FLOURECENTS. |