Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T04OT00012

Parcel: 10512024D


Addresses:

4066 N ORACLE RD

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
08/20/2004 SIGN ELECTRIC Approved IVRS - Inspection :*
08/03/2004 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*/ 1) NEED ACCESS-PLEASE PROVIDE A STEP LADDER
06/17/2004 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection :*/ 1) ACCESS IS NEEDED AS PER 600-21. 2) SUPPORT FLEX CONDUIT AS PER CODE. 3) BOND SPLICES AS PER CODE 600-7. 4) FINISH ITEMS 1 & 2 OF PREVIOUS INSP.
06/01/2004 SIGN ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) DISCONNECT SWITCH TO BE WITHIN SITE OF SIGN OR A LOCKABLE MEANS TO BE PROVIDED. 600-6. 2) WHERE IS MARKING LABEL 600-4? 3) PLEASE PROVIDE ACCESS TO INSPECT INSTALLATION WORK.